Commercial battery storage and energy arbitrage in Cape Town
First Energy Solar Solutions – engineer-led solar installers, Western Cape
A commercial battery earns its keep in three ways: it moves energy from cheap hours to expensive hours (energy arbitrage), it trims the monthly maximum-demand charge (peak shaving), and it stores midday commercial solar that would otherwise be exported or wasted. On the City of Cape Town’s 2026/27 time-of-use tariffs the gap between winter peak and off-peak energy is almost R6 per kWh, which is why batteries that made no financial sense a few years ago are now worth a proper calculation.
They are not right for every business, though. This page sets out where battery storage pays, where it does not, how we calculate the saving and what data we need from you to do it properly.
How energy arbitrage works on a Cape Town time-of-use tariff
Larger businesses in Cape Town are billed on a Large Power User time-of-use tariff. The price of a kWh depends on when you use it, and there is a separate charge for your highest demand in the month. These are the City’s 2026/27 low-voltage rates, excluding VAT:
| Large Power User LV time-of-use (ex VAT) | High demand (Jun – Aug) | Low demand (Sep – May) |
|---|---|---|
| Peak energy | 779.70 c/kWh | 362.58 c/kWh |
| Standard energy | 244.92 c/kWh | 233.02 c/kWh |
| Off-peak energy | 185.49 c/kWh | 185.49 c/kWh |
| Demand charge | R254.76 per kVA of measured monthly maximum demand | |
Peak hours are weekdays 07:00 – 09:00 and 18:00 – 21:00. Source: City of Cape Town 2026/27 electricity tariff schedule. Medium-voltage rates are slightly lower, and you should always check the figures against your own bill.
Arbitrage is simply charging the battery when energy is cheap – overnight at the off-peak rate, or at midday from your own solar – and discharging it in the peak hours so that you buy as little peak energy as possible.
How the savings are calculated: a worked example
Take 100 kWh of usable battery capacity discharged once every weekday into the peak periods, recharged from the grid at the off-peak rate, with a round-trip efficiency of 90% (so about 111 kWh of charging for every 100 kWh delivered).
| Per 100 kWh shifted (ex VAT) | Winter weekday | Summer weekday |
|---|---|---|
| Peak energy avoided | R780 | R363 |
| Cost of off-peak charging | R206 | R206 |
| Net saving per weekday | R574 | R156 |
| Weekdays in the season | about 65 | about 196 |
| Saving for the season | about R37,300 | about R30,700 |
That is roughly R68,000 a year for every 100 kWh shifted from energy arbitrage alone. Two things can lift it substantially:
- Charging from surplus solar. If the battery is filled by midday solar that you could not otherwise use, the charging cost falls away and the same 100 kWh is worth about R121,700 a year.
- Peak shaving. Every kVA you take off your monthly maximum demand saves R254.76 a month. A battery that reliably holds a site 50 kVA below its usual peak saves about R12,700 a month – but it has to do so in every half-hour of the month, which is why we size this from your interval data rather than from an average.
Batteries pay back fastest as part of a combined solar and storage system. On a recent proposal for a large commercial building on a time-of-use tariff – 777 kWp of solar with 2,410 kWh of battery storage – the modelled payback for the whole system was about 3.4 years. Roughly two-thirds of the saving came from solar and one-third from battery arbitrage, before counting any reduction in demand charges.
These figures are illustrative, based on the published tariff, and are not a quote. Your real saving depends on how much energy you actually use in peak hours, the shape of your demand, and the installed cost of the system, which we set against the saving to give you a payback period. For the solar side of the calculation see our guide to commercial solar cost and ROI in Cape Town.
Where commercial battery storage makes financial sense
- You are on a time-of-use tariff with a demand charge and use a meaningful amount of energy in the weekday morning and evening peaks – cold storage, manufacturing with early or late shifts, retail, hospitality, residential blocks and estates.
- You have solar that produces more than you use at midday, especially on weekends or shutdown days, or the City has limited how much you may export.
- Your bill shows short, sharp demand peaks – compressors, pumps or ovens starting together – that a battery can flatten.
- Outages cost you money. If lost production, spoiled stock or generator diesel has a real rand value, backup is a second income stream for the same battery.
- Your supply is at its limit. A battery can cover peaks that would otherwise need a costly upgrade to your notified maximum demand.
When a battery does not make sense
- You are on a flat-rate tariff. Small Power User tariffs charge the same price all day, so there is no price gap to arbitrage. Solar on its own nearly always gives a better return there.
- Your load is almost all daytime and solar already covers it. There is little peak energy left to shift.
- Your demand is flat and steady. With no peaks to shave, the demand-charge saving is small.
- You only expect to use it in winter. Summer arbitrage is worth roughly a quarter of winter arbitrage per day, so the system has to work all year, ideally with solar, to pay back.
- You have not installed solar yet. In most cases solar first, battery second, gives the faster payback – we will tell you if that is the case.
If the numbers do not work for your site we will say so. A battery that is too large for the load simply takes longer to pay for itself.
What we need from you for an assessment
- Your last 12 months of electricity bills, showing the tariff, notified maximum demand and monthly demand readings.
- Half-hourly interval (load profile) data from your meter if it is available – we can help you request it from the City or Eskom.
- Generation data from any existing solar system, and details of the inverters installed.
- Your operating hours, shift patterns and any planned changes to the site.
- Which loads must stay on during an outage, and for how long.
- Access to the main distribution board and a possible battery location for the site visit.
From this we model the battery against your actual load, half-hour by half-hour, and give you the recommended size, the expected annual saving split into arbitrage, demand and solar, the installed cost and the payback period.
How First Energy designs and installs commercial storage
First Energy is an engineer-led installer that has been operating since 2019, with commercial and industrial systems across the Western Cape, including a 300 kW industrial rooftop in Paarl and a 100 kW installation in Rosebank, Cape Town. Batteries can be added to an existing solar system or designed in from the start, and every system is registered with the City of Cape Town or Eskom – see our SSEG registration guide. Our batteries carry a 6,000-cycle warranty, which at one full cycle a day is more than 16 years of use, alongside 10 years on inverters and 3 years on workmanship. Read more about how we install.
Frequently asked questions
What is energy arbitrage?
Energy arbitrage is charging a battery when electricity is cheap and using that stored energy when electricity is expensive. On a City of Cape Town time-of-use tariff that means charging off-peak or from solar and discharging in the weekday peak periods.
Is a commercial battery worth it without solar?
Sometimes. On a time-of-use tariff with a demand charge, a battery can pay through arbitrage and peak shaving alone, but the return is usually better when it is paired with solar, because the charging energy is then close to free.
Does battery storage work on a flat-rate business tariff?
Not for arbitrage. A flat-rate tariff has no cheap and expensive hours, so a battery only adds value by storing surplus solar and providing backup power.
How big a battery does my business need?
It depends on how much energy you use in peak hours and how high your demand peaks are. We size the battery from your half-hourly meter data so that it cycles fully on most days rather than sitting partly unused.
How long does a commercial battery last?
The lithium batteries we install are warranted for 6,000 cycles. At one full cycle per day that is more than 16 years.
Do I need permission to add a battery?
Yes. A battery on a grid-connected inverter forms part of your embedded generation system and must be registered with the City of Cape Town or Eskom. First Energy handles the application as part of the installation.

Send us your bills and we will tell you whether a battery pays on your site. Contact us if you have any questions.